Steam Pipe Sizing for Large Steam Mains and Superheated Steam

How to use the Steam Pipe Sizing Chart

Example:
Required to size a pipe to handle 20 tonnes of steam per hour at a pressure of 14 bar gauge and a temperature of 340°C.
The length of the line is 300 metres and the permissable pressure drop over this length is 0.675 bar.

Note that the chart is in absolute pressure and for an exercise of this kind it is reasonable to assume that 14 bar gauge equals 15 bar absolute.

First find the pressure drop ratio

RATIO = PRESSURE DROP / INLET PRESSURE (ab.)
= 0.675 / 15
= 0.045

From this point on the left hand scale read horizontally to the right and at the intersection with the curved line read vertically upwards to meet the length line of 300 metres. At this point extend a horizontal line h1 h2 across the chart.
Now from the base temperature line at 340ºC extend upwards to meet the 15 bar abs. pressure line.

Read horizontally to the right to meet the capacity line of 20 tonnes/h and from this point extend a line vertically upwards. Where this intersects the line h1 h2 indicates the pipe size required.
Where this intersection comes between two pipe sizes, the larger should be used. The procedure can of course be reversed to find the pressure drop in a known pipe size.

Warm-up Load in Kilograms of Steam per 100 M of Steam Mains

Ambient Temperature 21ºC

Steam Pressure bar

50

mm

65

mm

80

mm

100

mm

125

mm

150

mm

Main size

300

mm

350

mm

400

mm

450

mm

500

mm

600

mm

 

-18C

Correction

200

mm

250

mm

Factor

 

0.00

9.2

14.4

19.0

27

37

47

71

101

134

159

208

262

308

309

1.50

0.35

10.0

15.9

20.8

29

40

52

69

112

146

174

227

287

338

470

1.45

0.70

11.3

17.8

23.4

33

45

58

88

125

165

196

255

322

379

529

1.41

1.00

12.2

19.5

25.4

36

50

64

96

135

179

212

277

350

412

575

1.39

2.50

13.4

21.3

27.8

39

53

70

105

148

195

232

303

383

450

627

1.33

4.00

15.8

25.2

33.0

47

63

82

123

175

233

276

360

454

535

745

1.30

5.50

17.8

28.0

37.0

52

71

92

138

196

260

308

402

507

598

832

1.28

7.00

19.3

30.6

40.0

57

77

100

151

214

284

335

438

553

651

906

1.26

8.50

20.1

31.8

42.0

59

80

104

157

223

293

349

455

574

676

942

1.25

10.00

20.8

33.1

43.0

62

83

108

162

230

305

361

472

595

700

997

1.24

12.00

22.6

35.8

47.0

67

90

117

176

250

331

392

513

646

760

1059

1.23

14.00

24.2

38.2

50.0

71

96

125

189

267

353

418

546

689

811

1130

1.22

16 00

28.1

45.0

58.0

83

113

146

219

312

412

489

638

805

947

1320

1.21

20.00

36.0

55.0

74.0

108

150

205

312

463

637

764

981

1228

1503

1700

1.20

25.00

39.0

59.0

80.0

117

162

222

338

502

692

828

1065

1362

1631

2315

1.19

30.00

41.5

64.0

85.0

124

173

237

360

534

735

882

1134

1420

1735

2464

1.18

40.00

44.3

68.0

91.0

132

184

253

385

570

784

940

1210

1514

1852

2627

1.17

* For outdoor temperature of -18ºC, multiply load value in table for each main size by correction factor shown.